NQOD Circuit
Breaker Interior
NQOD circuit breaker interiors are for use on ac systems
and are UL Listed under File E33139. NQOD circuit breaker interiors accept
QO®
and QOB branch circuit breakers.
Features
NQOD circuit breaker interior features include:
- 240 Vac maximum
- 600 A maximum vertical main circuit breakers
- 600 A maximum lugs
- 150 A maximum main lugs
- 30, 42, and 54 circuit interiors
- 10—65 kA maximum RMS symmetrical amperes short
circuit current rating (SCCR)
- Fully rated or series rated systems
- Copper or aluminum plated bus interiors
- Bolt-on or plug-on branch circuit breakers
- Interiors may be mounted for top or bottom feed
- Branch user placement
- VISI-TRIP® indicator on branch circuit breakers
- Suitable for use as service equipment
Options
- 200% rated neutrals up to 225 A
- Split bus interiors
- 1000 A/in2 copper bus
- 750 A/in2 aluminum bus
- Sub-feed and through-feed lugs
- Sub-feed circuit breakers
- TVSS
units
|