A new
generation of soft starts.
The Altistart 48 (ATS48) soft start features
a patented advanced motor control algorithm called TCS or Torque Control
System. Without speed feedback, the ATS48 soft start provides constant
starting and stopping rates independent of motor loading, just like a
more expensive AC drive. Setting the new industry standard for soft starts,
the ATS48 controls the applied motor torque, making it ideal for a wider
variety of applications than a traditional voltage ramp soft start with
the current limit. In pumping applications, the ATS48 with TCS eliminates
the long start and stop times, the hydraulic transients and slamming of
check valves associated with "pump version" voltage ramp soft
starts.
Ease of selection
Every ATS 48 soft start model is rated for all North American industrial
and commercial voltages — 208, 240, 480, and 600V. It is available
in 21 power ratings from 17 to 1200 amps and is available for every standard
motor rating up to 1000 HP at 460 VAC. No oversizing is required. Product
selection comes down to a simple selection of motor horsepower and duty
cycle.
Features and benefits
- Easy to install — Two or three wire control,
contactor style wiring, bypass contactor control, no separate overload
required, use in ambients up to 140ºF
- Preset for quick and easy start-up without adjustments
for the majority of applications
- Integrated and optional IP65 rated remote mounted
digital keypads for configuration and monitoring
- Ease of programming — Utilizes PowerSuite™
programming software, common to all Schneider Electric AC drives and
soft starts, for configuration, documentation, and archiving
- Complete motor and machine protection: motor overload
(classes 2 – 30), ground fault, excessive number of starts, stalled
motor, motor underload, machine overtorque, input and output phase loss,
phase reversal, and more…
- Rugged construction with the highest rated power
devices (SCRs) in the industry: 1800 PIV
- Generator friendly — Compatible with classes
1, 2, and 3 generators with wide frequency tolerance (60 Hz +/- 20%)
- Accepted internationally — Meets UL, CSA, CE,
NOM, CCC, C-Tick, GHOST, DNV
- Catch on the fly, regenerative braking
- Elapsed time meter, kilowatt hour meter
- Networking for remote monitoring and control: Modbus,
Ethernet, DeviceNet, and other protocols
|