Type 2 Coordination Schneider Electric And FERRAZ-SHAWMUT
TeSys D Line, IEC Starter with Class 10 Overload Relay Fuse Selection Table

The data found on this table was obtained from tests witnessed by representatives of UL and CSA. How to use this table: For each horsepower a combination contactor-overload relay and MAX fuses protection to obtain Type 2 Coordination is given. In normal application, fuses of a lower rating selected in accordance with the requirements of the National Electrical Code section 430.52(c)(1) and of the Canadian Electrical Code Rule 28-200 are to be used. A contactor of a larger size or an overload of a lower rating within the same family (i.e. LRD12 in lieu of LRD 14 or LRD 3359 in lieu of LRD 3361) can be used and still maintain the Type 2 coordination level.

Note:Type 2 coordination permits tack welding of the contacts. In the event of tack welding, the tack weld can be broken by operating electrically the contactor, or by prying apart the welded contacts with a small screwdriver, or by tapping the front of the contactor with a rubber mallet.

 

THREE PHASE MOTOR HORSEPOWER        
200V
230V
460V
575V
    MAX FERRAZ-SHAWMUT FUSES
HP(FLC)
HP(FLC)
HP(FLC)
HP(FLC)
Contactor Overload Relay Class CC Class J
-
-
-
0.5 (0.9)
LC1D09 LRD05 ATDR 2.8 AJT 1.5
-
-
0.5 (1.1)
0.75 (1.3)
LC1D09 LRD06 ATDR 5 AJT 2
-
-
0.75 (1.6)
-
LC1D09 LRD06 ATDR 5 AJT 2
0.5 (2.5)
0.5 (2.2)
-
1 (1.7)
LC1D09 LRD07 ATDR 8 AJT 5
-
-
1 (2.1)
-
LC1D09 LRD07 ATDR 8 AJT 5
-
-
-
1.5 (2.4)
LC1D09 LRD07 ATDR 8 AJT 5
0.75 (3.7)
0.75 (3.2)
1.5 (3.0)
-
LC1D09 LRD08 ATDR 12 AJT 5
-
-
-
2 (2.7)
LC1D09 LRD08 ATDR 12 AJT 5
-
-
2 (3.4)
-
LC1D09 LRD08 ATDR 12 AJT 5
-
-
-
3 (3.9)
LC1D09 LRD08 ATDR 12 AJT 5
1 (4.8)
1 (4.2)
3 (4.8)
-
LC1D09 LRD10 ATDR 30 AJT 20
1.5 (6.4)
1.5 (6.0)
-
5 (6.1)
LC1D09 LRD12 ATDR 30 AJT 20
2 (7.8)
2 (6.8)
-
-
LC1D09 LRD12 ATDR 30 AJT 20
-
-
5 (7.6)
-
LC1D09 LRD14 ATDR 30 AJT 20
-
-
-
7.5 (9.0)
LC1D12 LRD16 ATDR 30 AJT 20
3 (11.0)
3 (9.6)
7.5 (11.0)
-
LC1D12 LRD16 ATDR 30 AJT 20
-
-
-
10 (11.0)
LC1D18 LRD16 ATDR 30 AJT 20
10 (14.0)
LC1D18 LRD21
-
AJT 25
15 (17.0)
LC1 D25 LRD21
-
AJT 25
15 (21.0)
LC1D25 LRD22
-
AJT 35
15 (21.0)
LC1D32 LRD22
-
AJT 40
20 (22.0)
LC1D32 LRD22
-
AJT 40
20 (27.0)
   
-
 
25 (27.0)
   
-
 
10 (32.2)
10 (28.0)
25 (34)
-
LC1 D40 LRD3355
-
AJT 60
-
-
-
30 (32)
LC1D40 LRD3355
-
AJT 60
-
-
30 (40)
-
LC1D40 LRD3355
-
AJT 60
-
-
30 (40)
-
LC1D40 LRD3357
-
AJT 70
15 (48.3)
15 (42.0)
-
40 (41)
LC1D50 LRD3357
-
AJT 70
-
-
40 (52)
-
LC1D50 LRD3359
-
AJT 70
20 (62.1)
20 (54.0)
-
50 (52)
LC1D65 LRD3359
-
AJT 100
-
-
50 (65)
-
LC1D65 LRD3359
-
AJT 100
-
-
-
60 (62)
   
-
 
25 (78.2)
25 (68.0)
60 (77)
-
LC1D80 LRD3363
-
AJT 110
-
30 (80.0)
-
-
LC1D80 LRD3363
-
AJT 110
-
-
-
75 (77)
LC1D115 LR9D5367
-
AJT 125
30 (92.0)
40 (104)
75 (96)
-
LC1D115 LR9D5369
-
AJT 150
-
-
-
100 (99)
LC1D115 LR9D5369
-
AJT 150
40 (120)
-
100 (124)
-
LC1D150 LR9D5369
-
AJT 200
-
-
-
125 (125)
LC1D150 LR9D5369
-
AJT 200