A Square D exclusive -- the Micrologic ground-fault module is a UL® Listed circuit breaker accessory. It is a combination ground-fault relay and ground-fault sensing device. They are available for the PowerPact® H- and J-Frame molded case circuit breakers, as well as the FA, KA, FC, KC and KI type circuit breakers.
Features for all Micrologic GFMs include:
- Field-installed on molded case circuit breaker
- Adjustable ground-fault pickup levels (20 A to 200 A)
- Adjustable ground-fault time delays (instantaneous to 500 msec)
- Integral ground fault push-to-test feature and ground-fault indicator
- All ground-fault modules are supplied for I-Line® mounting; easily converted to unit-mounted
- Zone-selective interlocking capability with upstream Micrologic trip system circuit breakers is standard
- 120 Vac control power is required for integral test feature
- Meets NEC 230-95(c)
Features for only H&J GFMs include:
- Shunt trip for circuit breakers may be factory-installed or field-installed (12 Vdc) (Catalog Number S29382)
- Neutral current transformer for 3-phase, 4-wire applications is optional
Features for only FA, KA, FC, KC and KI type GFMs include:
- Circuit breakers must have factory-installed ground-fault shunt trip
- Neutral current transformer for 3-phase, 4-wire applications is included
|